Mitch’s Certified Classes

Cross Connection Control Specialist

CCCS-Final

Please enter the password provided by the Instructor below and select the "Start" button to begin.
By checking the box, I acknowledge that I have read, understand, and agree to comply with the Instructions and Conduct of Conduct provided by Mitch's Certified Classes, Inc.

1 / 50

1.The State Regulations mandate that the minimum distribution pressure at the point of delivery should be:

2 / 50

2. A situation where two or more water services are supplied to a single property is termed as:

3 / 50

3. Backflow preventers intended for hot water applications must be of a listed type and engineered to function at temperatures equal to or exceeding:

4 / 50

4. As per State Regulations, a Double-Check Valve Assembly is required to be installed above grade:

5 / 50

5. Per the State regulations, a Reduced Pressure Assembly should be installed at a maximum elevation of:

6 / 50

6. The rated flow for approved Backflow Assemblies are established by

7 / 50

7. A water line connected to a process steam line (no chemicals) may be safeguarded by:

8 / 50

8. The responsibility for establishing a list of acceptable backflow prevention assemblies for safeguarding a municipal water supply system lies with:

9 / 50

9. A Reduced Pressure Backflow Prevention Assembly should be positioned with a minimum elevation of:

10 / 50

10. Which of the following circumstances would primarily lead to water backflow through a cross-connection?

11 / 50

11. When should the initial test of a backflow prevention assembly be conducted?

12 / 50

12. What factor generally determines the type of backflow prevention assembly required?

13 / 50

13. What action should the Water Purveyor/Supplier take when access to a customer’s property is denied?

14 / 50

14. A Cross-Connection Control Program should include:

15 / 50

15. What components of public relations are crucial for the specialist to consider?

16 / 50

16. To qualify for Cross-Connection Control Program Specialist Certification, the candidate must initially hold:

17 / 50

17. Backflow prevention assemblies should not be situated in zones containing:

18 / 50

18. Who has been tasked with the responsibility and accountability for safeguarding the potable water distribution system?

19 / 50

19. When water to a critical service cannot be shut off even for a brief period, the backflow assembly should be:

20 / 50

20. Per the Uniform Plumbing Code, the method of rectifying a cross-connection to piping containing sewage would be:

21 / 50

21. As per the UPC, an air-gap on a two (2) inch spout, positioned four (4) inches from the side wall and two (2) inches from the back wall should be:

22 / 50

22. How many inches above the point of use should the PVB be installed?

23 / 50

23. For the correct installation of an atmospheric vacuum breaker (AVB) on an irrigation system, the down-stream piping can be elevated above the AVB under the condition that:

24 / 50

24. In cold climate areas, backflow assemblies shall be safeguarded from freezing by methods approved by:

25 / 50

25. A pollutant is considered:

26 / 50

26. The Uniform Plumbing Code (UPC) mandates that a Reduced Pressure Principle Backflow Prevention Assembly should be:

27 / 50

27. At locations where gray water is utilized, safeguarding the potable water system necessitates the installation of a/an:

28 / 50

28. The suggested position for installing a double-check valve assembly for service isolation is:

29 / 50

29. The concept of Air-Gap Separation refers to:

30 / 50

30. The responsibility for creating a list of certified backflow assembly testers lies with:

31 / 50

31. The objective of a double-check detector assembly, implemented on a fire sprinkler system, is to:

32 / 50

32. Which recognized organization approves backflow assemblies based on the successful completion of both field and laboratory evaluation?

33 / 50

33. When performing a cross-connection survey, the top priority for implementing backflow protection would be which of the following:

34 / 50

34. For air-gaps, the smallest cross-sectional area at the seat of the control valve or supply pipe or tubing that supplies the device or outlet is referred to as the:

35 / 50

35. When a single meter is arranged to enable internal piping to deliver both domestic water and either industrial water or fire sprinkler system water, this setup is termed as:

36 / 50

36. Which organization evaluates and approves backflow prevention assemblies through both laboratory and field assessments?

37 / 50

37. State Regulations require a Backflow Assembly Tester must:

38 / 50

38. After water has flowed through the connection from the public potable water system and is beyond the jurisdiction of the Water Purveyor/Supplier, it is categorized as:

39 / 50

39. The public or private entity responsible for supplying an approved water supply to the public is:

40 / 50

40. What type of backflow may occur through an indirect cross-connection?

41 / 50

41. What type of backflow is backsiphonage considered?

42 / 50

42. What is the primary purpose of a backflow assembly at the service connection?

43 / 50

43. What is the required number of test cocks for an approved Double-Check Valve Assembly?

44 / 50

44. What is the temperature designation for a Atmospheric Type Vacuum Breaker rated for cold water usage?

45 / 50

45. What regulates the types of recycled water and their approved use?

46 / 50

46. What is the pressure in a 40-foot vertical pipe when a perfect vacuum, at sea level, draws water up?

47 / 50

47. Which of the following connections is deemed improper?

48 / 50

48. State Regulations mandate that an authorized backflow preventer must be:

49 / 50

49. Backsiphonage resulting from an aspirator effect can be triggered by:

50 / 50

50. A reduced pressure backflow prevention assembly is described as:

Your score is

Exit