Mitch’s Certified Classes

Backflow Prevention Assembly Tester

BF-Final

Please enter the password provided by the Instructor below and select the "Start" button to begin.
By checking the box, I acknowledge that I have read, understand, and agree to comply with the Instructions and Conduct of Conduct provided by Mitch's Certified Classes, Inc.

1 / 50

1. What is Used Water:

2 / 50

2. What is Pollution:

3 / 50

3. What gauge reading would be a failure for the pressure differential relief valve:

4 / 50

4. When testing the RP, you close the high bleed then the low bleed and shut off the #2 shutoff valve. The differential pressure relief valve begins to discharge water, what does this indicate:

5 / 50

5. The pressure drop across the #1 check valve of an RP must be a minimum of at least?

6 / 50

6. A Cross-Connection is:

7 / 50

7. An Air-Gap is:

8 / 50

8. The proper way to vent air and debris from the test cocks of a reduced pressure backflow preventer is to:

9 / 50

9. When testing the opening point of the differential relief valve what happens:

10 / 50

10. Double-check – Detector Backflow Assemblies are on fire systems at service connections for what:

11 / 50

11. When testing the DC. The gauge must be maintained at:

12 / 50

12. When testing the DC and the #1 check valve reading is 0.5 psid, which of the following is true:

13 / 50

13. When testing DC. The #1 check valve reading is 0.8 psid and the #1 shut-off valve leaks, which of the following is true:

14 / 50

14. When testing #1 check valve of the DC, the sight tube should be attached to test cock #:

15 / 50

15. When testing the DC, and water continues to flow from test cock #3 when testing the #1 check valve, what does this indicate:

16 / 50

16. A pressure vacuum breaker must be installed how high above the down-stream piping:

17 / 50

17. When testing the air-inlet of a pressure vacuum breaker and it will not open, the cause is:

18 / 50

18. What values do you record when testing a pressure vacuum breaker:

19 / 50

19. Any shut-off valves on an atmospheric vacuum breaker must be installed:

20 / 50

20. Flushometers are required to have what type of backflow preventer for protection:

21 / 50

21. How high, above the down-stream piping, must an AVB be installed:

22 / 50

22. If water continues to flow from test cock #2 when testing a Pressure Vacuum Breaker, what does this indicate:

23 / 50

23. What is the second component of the Pressure Vacuum Breaker you test:

24 / 50

24. The vacuum breaker installed on a flushometer valve should be installed with the critical level at least how high above the water closet it is installed on:

25 / 50

25. The only place the State of California health department will accept a Pressure Vacuum Breaker for system protection is:

26 / 50

26. What are acceptable field test readings for a properly operating SVB:

27 / 50

27. SVB must be installed how high above the highest outlet:

28 / 50

28. While field testing the CV of a SVB, water continues to flow from vent valve, what does this imply:

29 / 50

29. The proper time to raise the test gauge to the DC, PVB, SVB assembly’s critical level is:

30 / 50

30. A SVB can be used for what type of hazard:

31 / 50

31. The term “Auxiliary Supply” means:

32 / 50

32. The two conditions that cause backflow to occur are:

33 / 50

33. A backflow preventer is required to be tested if:

34 / 50

34. A Double-Check Valve Assembly may be used:

35 / 50

35. If a cross-connection consisting of a direct connection between the sewer and a potable water system is discovered, the water agency can terminate the water service:

36 / 50

36. An atmospheric vacuum breaker can’t be used if the unit is under pressure for more than:

37 / 50

37. The best place to install a backflow preventer is:

38 / 50

38. Backflow into a drinking water line from a direct pressure connection to food processing line containing pancake syrup, under pressure from a circulating pump, may be prevented with the installation of:

39 / 50

39. The term “Air-Gap Separation” refers to:

40 / 50

40. It shall be the duty of the water user of any premise where backflow prevention assemblies are installed, to have competent inspection of the units made at least:

41 / 50

41. The water supply outlet of a proper air-gap requires the minimum distance above the overflow rim of a receptacle to be:

42 / 50

42. A water closet flushometer valve shall be equipped with an approved atmospheric vacuum breaker installed on the discharge side of the valve with the critical level above the overflow rim of the bowl being at least:

43 / 50

43. A vacuum breaker approved for hot water shall be designed to operate at temperatures above:

44 / 50

44. According to the Uniform Plumbing Code (UPC), any direct water connection to a sanitary sewer must be protected by:

45 / 50

45. What is the basic theory of a reduced pressure backflow preventer:

46 / 50

46. Backpressure Backflow is:

47 / 50

47. Backsiphonage Backflow is:

48 / 50

48. Shut-off valves and test cocks on approved reduced pressure backflow preventers must be:

49 / 50

49. A reduced pressure backflow preventer can be used to connect sewage to potable water when:

50 / 50

50. A reduced pressure backflow preventer consists of the following:

Your score is

Exit